1. Natural smoke discharge facilities cannot reach the purpose of smoke discharge
Natural smoke facilities cannot meet the purpose of smoking. Natural smoke discharge is an economical, simple, easy -to -operate, and convenient way to maintain management. However, because some projects do not conduct the requirements of specifications during the design and construction process, the project often leads to engineering.After the completion, the natural smoke discharge facilities do not have the effect of smoking. The main reasons are mainly in the following aspects:
Closey natural smoke window
1. Improper settings of natural smoke windows.Considering the effect of natural smoke, the smoke discharge windows should be set as close to the upper part of the wall as possible. At present, a considerable number of natural smoke discharge windows should not be set on the upper part of the wall, but the lower part.Smoke.
2. The open window area of ??natural smoke windows cannot meet the requirements.The standard "Fire Fire Standards for High -level Civil Building Design" clearly stipulates the area of ??open windows that use natural smoke, but because some designers have not carefully calculated according to the requirements of the specifications, or calculate the area of ??fixed windows on the area of ??the smoke window areaInside, the area of ??the smoke discharge windows of some projects fails to meet the requirements of the specifications, which directly affects the effect of smoking.
3. The structure of natural smoke windows is unreasonable.Some make the smoke discharge windows into an unstoppable fixed window, and some make the upper part of the window into a fixed window, and set the open smoke exhaust window to the lower part of the window, which seriously affects the smoke discharge function.
4. The lack of operating institutions that are convenient for opening the high height of installation.According to the requirements, the smoke discharge windows should be convenient to open, but some of the installation height should be installed and the difficulty of opening the operation device is not installed. It is not conducive to the opening of the smoke windows when it is not conducive to the fire.
Second, the effect of machine smoke discharge facilities is not obvious
The smoke exhaust effect of mechanical smoke discharge facilities does not obviously set the remaining pressure values ??required by the mechanical pressure and smoke -proof facilities.The phenomenon that does not meet the requirements of the specifications is more common in the project. Some wind speeds of airports and smoke discharge ports are even close to zero, which is more complicated to cause this phenomenon. There are mainly the following aspects:
Mechanical smoke exhaust system
1. Improper selection of fan.According to the requirements of the specifications, the volume of the staircase of the tobacco staircase and the front room, the front room, and the front room of the fire elevator room shall be determined by the calculation value. When the value of the calculation value and the specification specified is inconsistent, it shall be according to the inconsistency of the two among the two.The larger value is determined, and some designs are determined directly according to the values ??given by specifications, which often leads to the selected wind turbine air volume and wind pressure to be small and cannot meet the requirements.The design requires the selection of dual -speed fans; some construction units do not order the fans of the design, and the purchase of a fan with a small power specifications will cause the wind turbines air volume to be seriously insufficient.
2. Repeatable and duplicate settings of the mechanical pressure supply system and natural smoke discharge facilities.For a type of public building with a building height of more than 50 meters and living buildings with a height of more than 100 meters, according to the requirements of the "High Regulation", it is advisable to set up a mechanical pressure supply system.As a result, when the fire is in the fire, when the pressure supply system and natural smoke discharge windows are turned on at the same time, it is difficult to form positive pressure in the tobacco prevention floor and cannot achieve the smoke prevention effect.
3. The non -designed pressure difference regulating device is designed with a positive pressure supply system.According to the requirements of the specifications, the tobacco -proof staircase and the co -use front room of the controlled air supply should be set independently. When a system must be shared, the pressure difference between the pressure difference between the wind pipe leading to the front room should be set up.Adjust the device.At present, the combination of the positive pressure supply system of many designs does not have a design pressure difference. The residual pressure value of the staircase cannot be formed higher than the front room.
4. The smoke -proof partition does not set the smoke -shielding facilities according to the requirements of the specifications.There are a considerable part of the project, especially the large shopping malls set up mechanical tobacco sites without setting the smoke vertical wall under the ceiling according to the requirements of the specification.It is located on the wall of the ceiling or near the ceiling according to the requirements of the specification, but is located under the beam.
5. The setting of the air outlet does not meet the requirements.Some vertical anti -exhaust systems air outlets adopt a fixed -louver -window type constant air outlet. The size of the air outlet is basically the same, resulting in the wind speed of the air volume of the air outlets of each layer, which is seriously unbalanced.The wind speed and air volume of the air outlet is close to zero.
The construction quality of the wind duct is poor and the air leakage is serious.A considerable number of projects are not strictly connected due to ventilation and vertical wells. The closing of the air outlets is not tightly closed. The leakage is very serious, resulting in the wind speed and air volume of the air outlet, the wind speed and air volume of the smoke discharge outlet.The air duct connecting to the ceiling air inlet is canceled, and the ceiling stuffy roof space instead of the ducts often causes the airway air speed to approach zero.At the same time, some fans of the smoke exhaust system are located indoors, resulting in the discharge of smoke from the room to the room under the fire situation, which not only loses the smoke exhaust effect, but also may cause the fire to spread.
The above is the problem and solution that the fire discharge of smoke exhaust wind. If you want to know and learn more about the relevant knowledge, please pay more attention to us ——